China Plastics ›› 2012, Vol. 26 ›› Issue (10): 91-95 .DOI: 10.19491/j.issn.1001-9278.2012.10.014
Previous Articles Next Articles
Xuebao WANG Yang YANG
Received:
Revised:
Online:
Published:
Abstract: In this paper, the law of smoke release of cables under overload condition that frequently occurred in civil buildings was studied. The influence of overload current, conductor material, nominal sectional area, and the hardness of the cable on smoke release was discussed. It was found that the amount of smoke increaed with the increase of overload current. More smoke generated from coppercorewires than aluminum counterpart with the same diameter. The cables with smaller diameter and soft core were easier to release smoke than those with larger diameter and hard core.
Key words: cable, overload, smoke release, smoke density
Xuebao WANG Yang YANG. Experimental Study on the Law of Smoke Release of Cable Under Overload Condition[J]. China Plastics, 2012, 26(10): 91-95 .
0 / / Recommend
Add to citation manager EndNote|Ris|BibTeX
URL: https://www.plaschina.com.cn/EN/10.19491/j.issn.1001-9278.2012.10.014
https://www.plaschina.com.cn/EN/Y2012/V26/I10/91